1500 vdc cable installation on ladder tray

broken image

All cable trays shall be perforated or ladder type to avoid the retention of water and to allow fastening of the cables.Ĩ. Cable tray installation shall be designed to carry a load of 100kg/m. Distance between fixing points and cable tray support spacing shall be a maximum of three meter for ladder type tray and two meter maximum for perforated tray so as to avoid strain on cable trays.ħ. Cable trays shall be fixed onto standard steel shapes, welded to steel structures or fixed on to concrete structures with self-drilling dowels. On pipe racks, cable tray shall run on the top most level(s).Ħ. On horizontal cable trays, laid flat cables are fixed in group (one fastening for every two or three meters). On vertical cable trays and on edgewise – horizontal cable trays, each cable shall be fixed with 20mm wide stainless steel strips (two per meter). Only in special cases shall cable trays be installed vertically or on edge. Tray shall run as far as possible under flooring and walkways.

broken image
broken image

Cable tray installation shall preferably be installed flat in buildings or operating structures.